The iMAG 4700 flow meter is the most economical flanged electromagnetic flowmeter on the market. With electrodes designed to discourage fouling, it is available in 3” to 12” pipe in municipal or industrial water, waste and reclaimed water, pump stations, and packaged plant applications. Minimal straight pipe requirements allow the iMAG-Series flow meter to be used in piping configurations where there is little space between the meter and an elbow.
iMAG 4700 electromagnetic flow meter are CE certified, certified to NSF/ANSI standard 61, and are rated IP68 for applications where the meter may be operated underwater to a depth of at least 10 feet (3 meters) continuously.
The display can be meter mounted or remote, and both rate and total indication are standard. Rate and total units and pulse scaling can be set via the front panel touch keypad by the user. Bidirectional flow reading is standard with totals available in forward, reverse, net flow, batch forward flow, and batch reverse flow. Batch totals can be reset.
A power/output cable allows outputs for use with a variety of Seametrics and other displays and controls for remote reading and telemetry applications. The pulse output is standard on all models and 4-20mA passive current loop is standard on the iMAG 4700p. In addition, 4-20mA loop, HART protocol, high-speed digital, and Modbus® protocol outputs are optional on the externally powered units, depending on the model.
iMAG 4700 Features
- Quickly and easily change Total Volume Units, Flow Rate Units, Pulse Output Scaling, and many other settings using the two light sensor button controls on the display panel.
- Minimal straight pipe
- Mounted or remote rate & total
- Tamper-evident seal
- Certified to NSF/ANSI standard 61
- IP68 rated
- No moving parts
- Built-in Data Logger (Optional)
- Bidirectional Flow Reading (Standard)
- Pulse Scaled Output (Standard)
- 4-20mA Output (Optional*)
- HART Protocol Output (Optional*)
- Modbus® Protocol Output (Optional*)
- High-Speed Digital Output (Optional*)
- External DC Power (Optional*)
- Integrated AC Power Supply (Optional*)
- Remote Display (iMAG 4700r)
Application
RIGHT METER FOR :
- Water & Wastewater
- Treatment
- Municipal
- Pump skids
- Pump stations
- Packaged plants
- Filtration systems
- Reclaimed water
- Hydraulic fracturing
iMAG 4700 Specifications
- Pipe Sizes : 3”, 4”, 6”, 8”, 10”, 12”
- Flanges: 150 lb. ANSI Pattern
- Pressure: 150 psi (10.3 bar) line pressure
- Temperature
- Operating: 10˚ to 140˚ F (-12˚ to 60˚ C)
- Storage -40˚ to 158˚ F (-40˚ to 70˚ C)
- Accuracy: ±1.0% iMAG 4700), ±0.025% of the full-scale flow from low flow cutoff to maxi. a flow rate of 10 m/sec
- Low Flow Cutoff: 0.5% of the maximum flow rate
- Material
- Body Size 3” Ductile cast iron, powder-coated
- Body Size 4”-12” Welded steel, epoxy-coated
- Liner Size 3” Noryl®
- Liner Size 4”-12” Santoprene flange/Polypropylene liner body
- Material Electronics Housing: Powder-coated diecast aluminum
- Electrodes: 316 stainless steel
- O-ring (3” only) EPDM
- Display :
- Type 128×64 dot-matrix LCD
- Digits 5 Digit Rate and 8 Digit Total
- Units :
- Volume: Gallons, Liters, Barrels(42 gals), Cubic Feet, Cubic Meters, Million Gallons2 Mega Liters, Imperial Gallons, Million Imperial, Gallons
- Time: Second, Minute, Hour, Day
- Bidirectional: Forward Total, Reverse Total, Net Total, Batch Forward Total, Batch Reverse Total (Batch totals can be reset)
- Power:
- DC Power 9-36 Vdc @ 250 mA max, 30 mA average
- Battery Backup (Not for use as primary power)
- DC powered units: One lithium 7.2V ‘D’ size battery pack, replaceable.
- AC powered units: One 9V alkaline battery, replaceable.
Another Article: |
- Scaled Pulse Output
- Signal Current sinking pulse, isolated, 36 Vdc at 10 mA max
- Pulse Rates User-scalable from 0.1 to 99,999.9 volume units/pulse. Pulse width is one-half of the pulse period with a minimum pulse width of 2.5 ms, 200 pulses/sec max. For battery option meters, pulse width varies with frequency, 150 pulses/sec max.
- Output Options
- 4-20mA Current Loop Isolated, passive, 24Vdc, 650 Ω maximum current loop
- HART/4-20mA HART protocol over 4-20mA line
- High-Speed Digital Output: Isolated, open collector, 24 Vdc
- Serial Communications Isolated, asynchronous serial RS485 (Reconfigurable for RS232 or 3.3V CMOS), Modbus® RTU protocol (factory selectable)
- Cable Power/Output Cable 20ft (6m) standard length polyurethane jacketed cable—for power and outputs (lengths up to 200’ available).
- Conductivity >20 micro siemens/cm
- Empty Pipe Detection Hardware/software, conductivity-based
- Regulatory (EN 61326), 4”-12” certified to NSF/ANSI standard 61 60°C (140°F); 3” certified to NSF/ANSI standard 61 Cold Water 23°C (73.4°F)
- Environmental NEMA 6P, IP68 (10ft (3m) depth, continuously)