Valcom VSD4 Sanitary Digital Differential Pressure Transmitter

Posted by:

|

On:

|

Valcom VSD4 Sanitary Digital Differential Pressure Transmitter Can be specified within the range of 50 kPa to 1000 kPa of rated capacity. It’s suitable combine by batch control/PID Controller which need pulse output 4-20mA

  • Determines differential pressure by computing the outputs from two pressure sensors.
  • Output 4-20mA (2 wire system) scaling function.
  • Chooses from One output (Only the output of difference pressure) and Two output (The output of difference pressure + The Output of low-pressure side)
  • Pressure port with higher strength.
  • Safe and reliable construction with no sealed liquid.
  • Standard functions
    • Display switch (Differential pressure, High pressure, Low pressure)
    • Damping
    • Loop check function
    • FIX zero
    • Zero shift
    • Maximum/Minimum monitoring function
    • Setting output status at error
    • Key lock function

Specification

Display 7 segment 4-digit LCD display Character height: Approx. 12.7mm
Display range Approx. 3.5 times/sec.
Accuracy at room temperature(*1)
(Including Nonlinearity, Hysteresis, and repeatability)
Differential pressure Scaling in 20–100%R.C.: ±0.7%F.S.±1digit.
Scaling in 10–20%R.C.: ±1.4%F.S.±1digit.
Low pressure 2 output Scaling in 20–100%R.C.: ±0.5%F.S.±1digit.
Scaling in 10–20%R.C.: ±1%F.S.±1digit.
1 output
(Without analog output)
±0.5%F.S.±1digit.
High pressure
(Without analog output)
±0.5%R.C.±1digit.
Temperature compensation range (Sensor assembly) -5–150°C (Measurement pressure medium)
Safe temperature range (Sensor assembly) -5–150°C (Measurement pressure medium)
Temperature effect on zero balance ±0.6%R.C./10°C or less (Rated 300kPa, 500kPa, 1000kPa)
±0.7%R.C./10°C or less (Rated 50kPa, 100kPa, 200kPa)
Temperature effect on load ±0.6%R.C./10°C or less (Rated 300kPa, 500kPa, 1000kPa)
±0.7%R.C./10°C or less (Rated 50kPa, 100kPa, 200kPa)
Ambient temperature and humidity range 0–50°C (No condensation or freezing)
Material Case part: Aluminum die casting,
Front sheet part: PET
Radiating fin and adapter part: SUS304
IP Rating Equivalent to IP67
Mass Approx. 670g
Accessories Operating manual 1 copy, Test report 1 copy, Cable gland
Brackets for exclusive use of the PP type
U character bolt for brackets for exclusive use of the PP type
Hexagon nut for PP type fixation
  • (*1)For the ferrule type, zero adjustments is to be made after the clamp is tightened.

For more info and price please contact marketing@wmablog,com

 